[-] Show simple item record

dc.contributor.advisorO'Connell, Robert M., 1949-eng
dc.contributor.authorWacharasindhu, Tongtaweeeng
dc.date.issued2006eng
dc.date.submitted2006 Falleng
dc.descriptionThe entire dissertation/thesis text is included in the research.pdf file; the official abstract appears in the short.pdf file (which also appears in the research.pdf); a non-technical general description, or public abstract, appears in the public.pdf file.eng
dc.descriptionTitle from title screen of research.pdf file (viewed on August 29, 2007)eng
dc.descriptionIncludes bibliographical references.eng
dc.descriptionThesis (M.S.) University of Missouri-Columbia 2006.eng
dc.descriptionDissertations, Academic -- University of Missouri--Columbia -- Electrical engineering.eng
dc.description.abstractThe explosion of fuse holders at a certain 161 kV: 34.5 kV Ameren UE substation in the Potosi area was investigated. The Alternative Transients Program -Electromagnetic Transients Program (ATP-EMTP) was used to model and simulate the electrical behavior of transient overcurrents and overvoltages created by switching events in an effort to identify the cause of damage to a certain fuse holder used to protect the 4.5 MVAR capacitor bank on the 34.5 kV side of the transformer. Simulation results indicated that switching can increase the peak of the transient overcurrent from the normal current operation by up to9.33 p.u. Thus, the switching phenomenon may play a role in fuse holder damage.eng
dc.identifier.merlinb5945295xeng
dc.identifier.oclc166384398eng
dc.identifier.urihttps://hdl.handle.net/10355/4599
dc.identifier.urihttps://doi.org/10.32469/10355/4599eng
dc.languageEnglisheng
dc.publisherUniversity of Missouri--Columbiaeng
dc.relation.ispartofcommunityUniversity of Missouri--Columbia. Graduate School. Theses and Dissertationseng
dc.subject.lcshCapacitor bankseng
dc.subject.lcshElectric transformerseng
dc.subject.lcshElectric fuseseng
dc.subject.lcshSwitching power supplieseng
dc.subject.lcshExplosionproof electric transformerseng
dc.titleFuse holder damage investigationeng